Adlink ND-6024 Bedienungsanleitung Seite 32

  • Herunterladen
  • Zu meinen Handbüchern hinzufügen
  • Drucken
  • Seite
    / 65
  • Inhaltsverzeichnis
  • LESEZEICHEN
  • Bewertet. / 5. Basierend auf Kundenbewertungen
Seitenansicht 31
26
Command Set
3.3 Read Configuration
@Description
Read the configuration of module on a specified address ID.
@Syntax
$(Addr)2<CR>
$
Command leading code
(Addr)
Address ID.
2
Command code for reading configuration
@Response
!(Addr)(OutputRange)(BaudRate)(DataFormat)<CR>
or
?(Addr)<CR>
!
Command is valid.
?
Command is invalid.
(Addr)
Address ID.
(OutputRange)
Current setting of analog voltage output, refers
to Table 3-1 for details.
(BaudRate)
Current setting of communication baud rate,
refers to Table 3-2 for details.
(DataFormat)
Current settings of checksum, integration time
and output data format, refers to Figure 3-1 for
details.
@Example
User command: $182<CR>
Response: !18320610<CR>
!
Command is valid.
18
Address ID.
32
Analog output range is 0 to 10V
06
Baud rate is 9600 bps.
10
The output data is in engineering units, slew rate is
1mA/sec, checksum is disable.
Seitenansicht 31
1 2 ... 27 28 29 30 31 32 33 34 35 36 37 ... 64 65

Kommentare zu diesen Handbüchern

Keine Kommentare